Accuenergy Acuvim meter

Avatar

sdg.matiaan
2025-08-06 10:36
Last Edited 2025-08-06 14:36

To add the acuvim as a meter to send data via FTP, I assume you already have the CSV Server added.

You'll also need to add the axm-web2-d communication module on the device.


You need to get one of the files that the meter will push so that you can set up a template in PNPSCADA.
If you can get a file, you can download this one, however I don't know if your device is set up exactly the same, so the template might not work.
In PNPSCADA add the Device as a Virtual Meter.
Then go to Tools->Import Meter Readings.
Upload this file and save the configuration as accuvim.
Please note the date column needs to be set as Date/Time, not other options like 'yyyy-MM-dd'.
(You only need to create the template once, but each acuvim needs to be added separately as a Virtual Meter)



You can download the Manual here on how to setup the web2 module

Under Settings->Communications->Post Channel enter your settings.
Specifically under Customized Name enter the name as the [template name] / gateway / [serial number]
So in the example, the template name is accuvim and the serial number is CLD00000000.



Under Data Log choose Post Channel that you set up with FTP details.
And choose what must be posted.
Please note that 'Log File Length' determines the interval when files are sent. So best is probably '1 Day'




You can also switch on remote to be able to access the device remotely

You can find CSV upload logs under Reports->Various->CSV Log and CSV Queue


Tags: accuenergy acuvim