Itron ACE6000 VS Itron SL7000

Avatar

rudiemm
2012-02-14 09:00

The Itron ACE6000 is newer than the Itron SL7000. The Itron SL7000 had some issues that made it lees reliable for AMR.
We strongly recommend that if you should install Itron meters to rather go for the Itron ACE6000.

Avatar

sdg.marinusvz
2026-10-21 11:25
Last Edited 2026-10-21 11:27

Yes, sometimes the SL7000 has a thing called a 'Watchdog event', and then it wipes the load profile data for an entire day.


Even when we attempt to read it with the Meter Reading software of the manufacturer, the day is completely blank. The registers still counted up, but the load profile is just gone. This causes the meter not to audit.

I thought the SL7000 was newer than the ACE6000?

With both meters, reading the events seem problematic, because we were not able to do selective access, meaning we have to read the entire event log every time, so if your link is unreliable, you cannot read the events. The events are also in time sequence (from old to new), so the newest events are not even in the top of the returned data. So when doing IPT (Sparklet client mode), or accessing over less reliable networks, you invariable would lose connection in the middle of reading events. So in those cases, better to read everything else and not events! Switch off events in Advanced Meter Settings..