This post is a transcribed email. Details and been obfuscated to protect client privacy
Hi Marinus
This problem is persisting and it is will become a problem with billing.
Check below, this is what is happening.
sdg.marinusvz
2013-09-11 07:33
sdg.marinusvz
2013-09-11 07:34
There are many things you can try. How many meters are there with this problem?
You can try to improve the signal by moving the arial on the meter, you can try CSD, you can download the profile manually with a laptop and an optical probe, and upload the resultant profile into PNPSCADA on the appropriate screen, ....
Why would the BCC fail? If even CSD fails, you can try reading the profile with MAP110 or MAP120 remotely, because then that should also fail, at which point it becomes a non-PNPSCADA issue and you can call Landis and Gyr to ask them what to do.
So, what my advice is: