MetCom IEC Readout

Avatar

sdg.matiaan
2024-06-27 14:23
Last Edited 2024-11-19 10:11

For totals and phasor:
The OBIS codes we read from the MetCom is:

0.0.0
0.9.2
0.9.1
0.1.0
9.6.1
1.8.0
5.8.0
2.8.0
6.8.0
7.8.0
8.8.0
0.1.2
32.7.0
52.7.0
72.7.0
31.7.0
51.7.0
71.7.0
81.7.4
81.7.15
81.7.26


Tags: metcom
Avatar

sdg.matiaan
2024-11-19 09:36
Last Edited 2024-11-19 10:11

For profile:
For billing basic IBT you typically need to profile 1.8.0 (or 1.5.0).
For billing basic IBT and NET you typically need to profile 1.8.0 (or 1.5.0) and 2.8.0 (or 2.5.0).
For billing TOU and Demand you typically need to profile 1.8.0 (or 1.5.0) and 5.8.0 (or 5.5.0).
For full 4 quadrant metering you need to profile 1.8.0, 2.8.0 and 5.8.0 to 8.8.0.