you have to only read profile. Then it doesn't use the DC as a repeater to talk directly to the meter. (Switch off all other checkboxes on Edit->Advanced Meter Settings, all except Profile)
the rest goes through the DC to the meter, but profile it reads from the DC only. (I have tried in the beginning to read profile directly from the meter over the DC as a router also, but it stops working after about a week, and then you can only read it from the DC. With most other DCs, we go directly to the meter, but with the DCv3 from L+G that does not want to work)
Maybe the format of the profile for the meter on the DC and on the meter are different? That could cause problems.... The columns and profile period has to be set up the same for that meter on the meter itself, and for that meter on the DC.
One of the problems of course is that the DC doesn't keep as long a profile as on the meter itself, so if you can't read a meter for a month, you start to lose data... you can only get it back by going to site and reading it directly from the individual meter itself. You don't actually lose energy, since the profile for the E460s are meter totals, but you lose the profile.
I investigated one meter,
, the problem is there is only profile up to 25 August on the DC.
...which we have read ok, by the way. So it seems his problem is in fact, that the DC has NOT read the meter up to today.
So it is not good enough to say 'the DC has data for the meter', in fact it does have some, but not all of it.
so on all the meters on the DC, ONLY profile checkbox must be checked, NOTHING else, so that we don't put the DC or G3-PLC network under strain