sdg.marinusvz
2024-06-13 10:57
Last Edited 2024-06-13 11:07
I see the comunication attempt times out in the middle of receiving a packet:
sdg.marinusvz
2024-06-13 11:02
BCC not correct, asking for day's readings again
sdg.marinusvz
2024-06-13 11:04
corruption of communication channel.
sdg.marinusvz
2024-06-13 11:05
Last Edited 2024-06-13 11:06
I think this byte was dropped between the meter and the modem, since IPT does framing of sub-stream data packets, it implies that the framing worked without dropping the stream, and therefore the byte was lost before the modem framed the data packet. So it is not just the cell phone data stream that is stressed with IPT, but even the comms stream just between the L&G meter and L&G modem, in my opinion.
So, switching to a Generic APN modem would relieve the stress on the communications channel as a whole, not just within the cell phone network
With a partial reading, typically the 'Last Read Up to Date & Time' should have advanced. Once it has advanced to the current time, the meter is effectively 'read in' fully.
sdg.marinusvz
2024-06-13 11:15
we ended up getting progress with our sim cards (pay as you go public apn internet sim cards), not the private apn sim cards, so we decided to carry on with our sim cards on the IEC, not the DLMS. On many sites with the E650s, we're getting partial readings with it. So we're getting data, but it is just that partial reading, we're not getting the full reading.