If you are sure that the problem lies with us, then there is a way you can verify you have communications between the meter and the DC.
Open the DC in your web browser via its hotspot as detailed above, then click on the Debug button at the top. You have to go through another password authentication, for which the default password is also 123456. This will make your session go into Debug mode, which would enable new options in your configurator web site.
Go to Maintenance in the left hand menu, and the sub option of Gateway.
You will end up in a screen with 2 big text field columns. Above the left hand text field, would be some fields and 3 buttons.
Make sure the fields are:
MeterId (put in there your meter serial number, e.g. all 11 digits)
Class (should be 1)
OBIS (should be?0-0:96.1.0.255)
Attr (should be 2)
Then click on the blue 'Get' button.
In the right hand text field, it will start with something like:
->E6 00 0B 31 34 34 31 31 33 35 33 30 36 34 C0 01 C3 00 01 00 00 60 01 00 FF 02 00
then, if the meter exists and the DC can communicate to it, it will after a little bit of time also put a second line similar to this:
<-E7 00 0B 31 34 34 31 31 33 35 33 30 36 34 C0 01 C3 00 01 00 00 60 01 00 FF 02 00
but if the meter does NOT exist, or the DC CANNOT communicate to it for some reason, it will after some time put a second line like this:
<-E7 00 0B 31 34 34 31 31 33 35 33 30 36 35 D8 80 81
(notice the D8 in the third last byte)
In this way, the D8 return error can be verified using purely Hexing's own hardware, with our system not at all involved. Unless you can get this working, it is futile to try to get our system to communicate to the meter. If the DC doesn't see the meter, pnpscada would not be able to read the meter through the Data Concentrator. Please verify this communication first before calling us for support. And when talking to your manufacturer's support personnel, only mention using the mechanisms of the hardware and software of the manufacturer only, until you can get that working. Otherwise, it complicates the situation or they could blame us. But if the mechanism for which you seek support, only involves their own hardware and software, it is more difficult for them to shift the blame, and it makes it a lot easier for them to reproduce the problem and help you.
Tags: hxej200