rudiemm
2012-02-16 12:00
Answer:
That depends on the error. It could be that your 'Full Load' parameter on the 'Edit->Meter Details' screen is set too low, and therefore you're getting a lot of grey because it thinks you're going to trip or burn out your supply, because you're drawing too much current. Make sure this is set up right. Also make sure your CT and CT ratios and Primary/Secondary metering flag and the number of wires in the install, and everything else on the 'Meter Details' screen is set up correctly.
You'd normally not be able to fix bad status retro-actively, but in the case of a Meter Details screen that was set up wrong, you could fix it and set your 'Last Read Up to Date & Time' back, and then the new profile you read in will probably not have a bad status, so that could be one way to fix it retroactively. But most errors, you'll have to fix on site, e.g. a blown fuse, which would then be fixed in future, but the historic record can never be 'fixed'.
sdg.matiaan
2023-04-12 10:52